Panel Air Intake Filters & Filter Silencers

F21 / F22 / F41 / F42 Series

Air intake filter and filter silencer requirements vary with installation locations and type of foreign matter being removed from the air.  The F21 & F22 series are single or dual stage filtration while the F41 & F42 are a three stage HEPA level filtration. All filter elements have been designed to provide long life and minimum maintenance through careful selection for dry type filter media.  All filter elements have a heavy metal frame to withstand handling and moisture.

Filter housings are fabricated from heavy gauge sheet steel and plate.  To provide a weatherproof housing, it is welded and caulked as required.  Housings are supplied with outlet flanges dilled to match 125 lb. ANSI flanges and finished with a coat of machinery enamel.  Weather hoods are included with all models at no extra cost.  Pipe legs supports are a recommended and available option.  All models have a safety inlet screen installed to prevent any foreign objects from being drawn into the piping during filter changes.

F22 & F42 Air Intake Filter Silencers will provide adequate silencing for centrifugal compressors.  For equipment requiring better silencing, it is recommended that the F21 or F41 be used in series with a standard intake silencer.  Sales Engineers are available to assist in the selection of the correct size and type of filter element or to custom design equipment to meet your specifications.

1 & 2 Stage Filters

Application

The F22 Air Intake Filter Silencer is recommended primarily for use on centrifugal compressors and fans where it will provide adequate silencing as well as controlled air filtration. The silencer design incorporated in the filter housing is mainly effective on the higher frequencies and provides only a small amount of silencing in the low frequencies. The F21 Air Intake Filter is recommended for use on turbines, engines, centrifugal fans, blowers, and compressors where controlled filtration is required; however, an appropriate silencer must be installed between the air moving device and the filter/silencer.

Filter housings are available to accept either a single filter element or two filter elements in series. Internal design provides a safeguard to prevent small size foreign objects from entering the air intake passageway when filters are removed. Special designs available upon request.

F21 – Intake Filter

ModelPart #Total Filter Element (CFM)Number of 24″ x 24″ Element OpeningsOutlet Nozzle Velocity (FPM)Fig.AQCSWt. (Lbs.)Drawing
F21-8141A1422,50017,19818242934 7/8215Login to View
F21-10141A1432,50014,565110242934 7/8220Login to View
F21-12141A1442,50013,183112242934 7/8230Login to View
F21-12241A145
5,00026,365
212
24
2965.75330Login to View
F21-14241A1465,00024,940214242965.75340Login to View
F21-16241A1485,00023,755216242965.75350Login to View
F21-184
41A150
10,00045,900
318482965.75530Login to View
F21-20441A15110,00044,760320482965.75545Login to View
F21-24410,00043,280324482965.75570
F21-246
41A261
15,00064,920
424
482975.75640Login to View
F21-30641A15615,00063,135430482975.75675Login to View
F21-30841A15720,00084,180
530482975.75765Login to View
F21-36841A15820,00082,920536482975.75855Login to View

F22 – Intake Filter Silencer

ModelPart #Total Filter Element (CFM)Number of 24″ x 24″ Element OpeningsOutlet Nozzle Velocity (FPM)Fig.AQCSWt. (Lbs.)Drawing
F22-8143A1352,50017,19818243334 7/8270
Login to View
F22-10143A136
2,50014,565
110243334 7/8295Login to View
F22-12143A1372,50013,183112243334 7/8380Login to View
F22-12243A138

5,00026,365
212
24
3365.75425
Login to View
F22-14243A1395,00024,940214243365.75440Login to View
F22-16243A1405,00023,755216243365.75455Login to View
F22-184
43A143
10,00045,900
318483365.75645Login to View
F22-20443A14410,00044,760320483365.75650Login to View
F22-24410,00043,280324483365.75690
F22-246
43A153
15,00064,920
424
483375.75760Login to View
F22-30643A15415,00063,135430483375.75830Login to View
F22-30843A15520,00084,180530483375.75920Login to View
F22-36843A15620,00082,920536483375.751065Login to View

3-Stage HEPA Filters

Application

The F42 Air Intake Filter Silencer is recommended primarily for use on centrifugal compressors and fans where it will provide adequate silencing as well as dust-free process air. The silencer design incorporated in the filter housing is mainly effective on the higher frequencies and provides only a small amount of silencing in the low frequencies. The F41 Air Intake Filter is recommended for use on turbines, engines, centrifugal fans, blowers, and compressors where dust-free process air requirements are highly critical; however, an appropriate silencer must be installed between the air moving device and the filter/silencer.

The F41 & F42 Series employs a three-stage filtering system which consists of a Type F3 primary, a Type F4 intermediate and a Type F5 filter. The rigid housing is designed to accept 24˝ x 24˝ filter elements, wherein the final filter contains a fluid seal to prevent bypass. The minimum efficiency of the final filter is not less than 99.97% (by DOP test method) on 0.3 microns and above. Field tests indicate final filters need to be changed once every 18 to 24 months if the primary and intermediate filters are properly serviced. Special designs are available upon request.

F41 – Intake Filter

ModelTotal Filter Element (CFM)Number of 24″ x 24″ Element OpeningsOutlet Nozzle Velocity (FPM)Fig.AQCSWt. (Lbs.)No. of 24″ x 24″ Filter Elements (F3)No. of 24″ x 24″ Filter Elements (F4)No. of 24″ x 24″ Filter Elements (F5)
F41-812,50017,19818242946 7/8315111
F41-1012,50014,565110242946 7/8320111
F41-1212,50013,183112242946 7/8335111
F41-1225,00026,365
212
24
2969.75455222
F41-1425,00024,940214242969.75465222
F41-1625,00023,755216242981.75515222
F41-184
10,00045,900
318482981.75875444
F41-20410,00044,760320482981.75895444
F41-24410,00043,280324482981.75915444
F41-246
15,00064,920
424
4829102.751180666
F41-30615,00063,1354304829102.751215666
F41-30820,00084,180
5304829102.751415888
F41-36820,00082,9205364829102.751505888

F42 – Intake Filter Silencer

ModelTotal Filter Element (CFM)Number of 24″ x 24″ Element OpeningsOutlet Nozzle Velocity (FPM)Fig.AQCSWt. (Lbs.)No. of 24″ x 24″ Filter Elements (F3)No. of 24″ x 24″ Filter Elements (F4)No. of 24″ x 24″ Filter Elements (F5)
F42-812,50017,19818243350 7/8370111
F42-1012,50014,565110243350 7/8385111
F42-1212,50013,183112243350 7/8405
111
F42-1225,00026,365
212
24
3381.75555
222
F42-1425,00024,940214243381.75570222
F42-1625,00023,755216243381.75585222
F42-184
10,00045,900
318483381.75910444
F42-20410,00044,760320483381.75935444
F42-24410,00043,280324483393.751065444
F42-246
15,00064,920
424
4833102.751300666
F42-30615,00063,1354304833102.751370666
F42-30820,00084,180
5304833102.751570
888
F42-36820,00082,9205364833102.751695888

Panel Filter Element Options

Stoddard Filters - F2-106

F2-106 Washable Polyester Element (Standard)

  • Construction: 24˝ x 24˝ x 2˝ filter element with a washable polyester media, between a screen mesh and expanded metal grid on a galvanized metal frame.
  • Efficiency: 99% on 10 micron particles and larger.
  • Service: Rap out excessive dirt and wash in warm water containing a mild detergent. Rinse thoroughly and rap out excessive water. Replace in Filter Housing.
Stoddard Filters - F3-101 w A26-101

F3-101 Disposable Polyester Element

  • Construction: 24˝ x 24˝ x 2˝ filter element with a disposable polyester media, held in place with a galvanized metal holding frame, designed for easy media replacement.
  • Efficiency: 90% on 10 micron particles and larger.
  • Service: Replace disposable media when visually dirty. Replaceable polyester media is part number A26-101.
Stoddard Filters - F4-101

F4-101 Disposable Polyester Element

  • Construction: 24˝ x 24˝ x 3˝ filter element with a pleated paper media, held in place with a metal holding frame
  • Efficiency: 99% on 1 micron particles and larger.
  • Service: Clean by directing compressed air through filter in opposite direction to flow. (Do Not Wash in Water).

F5-101 Molded Glass HEPA Element

  • Construction: 24˝ x 24˝ x 11-1/2˝ filter element with a molded glass media bonded to a Galvaneal metal frame which has a fluid seal to eliminate bypass
  • Efficiency: 99.97% on 0.3 micron and above by DOP test method.
  • Service: Filter is not cleanable. If the Primary and Secondary filters are properly maintained, this filter should last 18 to 24 months.

Service Instructions

  1. Turn off air moving device prior to servicing.
  2. Remove fasteners on weatherhoods. Remove weatherhood.
  3. Check elements and service as shown above for the appropriate element.
  4. Check inside of housing for loose articles before replacing weatherhood.
  5. Replace weatherhood.
  6. Restart the air moving device.

Download Data Sheets

Download F21 & F41 Data Sheet Download F22 & F42 Data Sheet Air Intake Filter Fill-In Sheet